Transient Performance of Voltage Source Converter under Unbalanced Voltage Dips
Övrigt konferensbidrag, 2004

- Robust operation of Voltage Source Converters under unbalanced voltage dips can be obtained by controlling the positive and negative-sequence currents separately with a Dual Vector Current Controller (DVCC). In this paper, the performance of the DVCC is investigated under all voltage dips that can affect the converter. Two different methods for taking into account the oscillating powers dissipated in the filter are presented, tested and compared. The effect of the phase-angle jump of the dip is also studied.

unbalance

Voltage Source Converter (VSC)

voltage dip (sag)

current controller

Författare

Fainan Magueed

Chalmers, Institutionen för elteknik

Power electronics specilists PESC'04

Ämneskategorier

Elektroteknik och elektronik

Mer information

Skapat

2017-10-06