Capacitor voltage balance performance comparison of MMC-STATCOM using NLC and PS-PWM strategies during negative sequence current injection
Paper in proceeding, 2016

This paper addresses the modular multilevel converter applied as a static synchronous compensator. The main objective of this work is to compare the converter performance considering two different submodule capacitor voltage balancing strategies: nearest level control and phase-shifted pulse width modulation, during positive and negative sequence current injection. Results of a 15 MVA MMC STATCOM show that the nearest level control strategy has lower average switching frequency compared to the phase-shifted pulse width modulation strategy, considering comparable submodule capacitance voltage ripple.

Static Synchronous Compensator (STATCOM)

Multilevel converters

Modulation strategy

Reactive power

High voltage power converters

Author

H. A. Pereira

Federal University of Viçosa

A. F. Cupertino

Centro Federal de Educacao Tecnologica de Minas Gerais

L. S. Xavier

Federal University of Viçosa

A. Sangwongwanich

Aalborg University

L. Mathe

Aalborg University

Massimo Bongiorno

Chalmers, Energy and Environment, Electric Power Engineering

Remus Teodorescu

Aalborg University

18th European Conference on Power Electronics and Applications, EPE 2016 ECCE Europe, Karlsruhe, Germany, 5-9 September 2016

2325-0313 (ISSN)


978-9-0758-1524-5 (ISBN)

Subject Categories

Electrical Engineering, Electronic Engineering, Information Engineering

DOI

10.1109/EPE.2016.7695672

ISBN

978-9-0758-1524-5

More information

Latest update