VSC-HVDC system robust stability analysis based on a modified mixed small gain and passivity theorem
Paper in proceeding, 2017

In a VSC-HVDC system, when the input power to the converter is controlled to a positive constant, the converter acts a differential negative resistance — Po/i2 0, which may cause instability in case of a connected weak AC-grid. In order to analyze the robust stability of such a system, a modified mixed small gain and passivity theorem is proposed, which shows that the negative feedback interconnection of two linear time invariant stable subsystems (converter admittance and AC-grid impedance) is input to output stable if in certain frequency bands, both subsystems are passive and at least one of them is strictly passive; at the remaining frequency bands, the loop gain is to be strictly less than one. Under different AC-grid topologies, the stability sufficient conditions with respect to the AC-grid inductance are studied. It shows that for AC-grid consists of series RgLg-circuit, an introduced series capacitor can improve the system robustness but not for the shunt capacitor.

linearized model

AC-grid interaction

Robust stability of LTI systems

VSC-HVDC system

passivity

small gain

Author

Yujiao Song

Chalmers, Signals and Systems, Systems and control

Claes Breitholtz

Chalmers, Signals and Systems, Systems and control

IFAC-PapersOnLine

24058963 (eISSN)

Vol. 50 1 13-18

20th IFAC World Congress
Toulouse, France,

Subject Categories

Control Engineering

DOI

10.1016/j.ifacol.2017.08.003

More information

Latest update

7/4/2021 1