Lighting powers in shops and their effect on the energy performance of a shopping mall
Paper in proceeding, 2009

In this study, a multizone model of an existing shopping mall is developed in IDA Indoor Climate and Energy (IDA ICE). The model is validated using field measurements regarding use of energy for heating, sum of cooling and ventilation, operational electricity and tenant electricity. In addition, other input data used are energy use, operation hours, customer frequency, lighting, building envelope, HVAC system and control strategies. In this study, a parameter analysis regarding the building orientation, glazed façade area ratio and lighting is conducted. Results show that the shops' lighting powers dominate the cooling demand and imply that current internal loads decreases the sensitivity regarding energy demand of moderate changes in the glazed façades and building orientation.

Author

S. Stensson

SP Sveriges Tekniska Forskningsinstitut AB

Monica Axell

SP Sveriges Tekniska Forskningsinstitut AB

Per Fahlén

Chalmers, Energy and Environment, Building Services Engineering

Jörgen Eriksson

Simon Roos

Chalmers, Civil and Environmental Engineering, Building Technology

11th International IBPSA Conference - Building Simulation 2009, BS 2009; Glasgow; United Kingdom; 27 July 2007 through 30 July 2007

1260-1267

Subject Categories

Civil Engineering

More information

Latest update

9/6/2018 1