Three Phase Controlled Fault Interruption Using High Voltage SF6 Circuit Breakers
Doctoral thesis, 2007
A method is presented for implementing controlled fault interruption,
using high voltage, SF6 circuit breakers on three phase high voltage power
networks. The main goal of the method is to synchronize the opening or trip
commands to each phase of a circuit breaker with respect to target current
zero times so that each phase will interrupt with a preselected arcing
time. Benefits of this approach include reduction in the electrical wear
rate of the circuit breaker, in addition to providing potential to optimize
existing interrupter technologies and facilitate new interruption
techniques.
A generic structure for controlled fault interruption algorithms is
proposed, aimed at utilizing synergies with existing digital power system
protection methods. The proposed method is based on estimating the future
behavior of the currents in each phase, using a generic model. The
parameters of the model of the currents are obtained using least mean
squares regression. Novel features of the proposed method include the use
of analysis-of- variance tests to validate the model for targeting instant
selection, provision of algorithm failure bypass control, identification of
multiphase fault types and detection of the fault inception instant. A
comprehensive range of future work proposals is also provided.
Simulations have been made using the proposed method for a range of
multiphase fault cases than may occur on a three phase power network. The
results indicate that the method is capable of discriminating between
different fault cases and estimating target current zero times within ± 0.5
ms, within typical protection system response times of 5 to 20 ms, even
with large random noise distortion of the measured current signals.
High power experiments have also been conducted to investigate the
stability of the minimum arcing times of a high voltage, SF6 circuit
breaker, operated at 80% of its normal opening speed, for a wide range of
fault current interruption duties. The results of these experiments confirm
the viability of controlled fault interruption from the perspective of
minimum arcing time stability, in addition to indicating significant
potential for circuit breaker optimization by using the controlled fault
interruption technique to restrict the required arcing time window and
thereby also the required interrupter operating energy.
controlled switching
high voltage
hypothesis testing
circuit breakers
fault interruption
least mean squares regression
power system protection
Lecture room E:A, Hörsalsvägen 11, Chalmers
Opponent: Professor Dr Rene P. P. Smeets, Manager, T&D Testing, Product Development and Innovation, KEMA Nederland BV, Arnhem, the Netherlands