An optimal monitoring program for obtaining voltage sag system indexes
Artikel i vetenskaplig tidskrift, 2006

This paper presents a meter placement method for voltage sags monitoring in large transmission systems. An integer programming-based modeling is proposed for choosing the locations of power quality meters. A branch-and-bound-type algorithm is used to solve the optimization problem. A large transmission network is used to validate the method. Stochastic assessment of voltage sags is applied to the test network to obtain simulated monitoring results. Voltage sags system indexes are calculated from monitoring programs designed according to the optimization method. Comparisons with the system indexes obtained from a full monitoring program show the applicability of the method.

Författare

Gabriel Olguin

Chalmers, Energi och miljö

F. Vuinovich

Universita degli Studi di Palermo

M. H. J. Bollen

Luleå tekniska universitet

IEEE Transactions on Power Systems

0885-8950 (ISSN) 15580679 (eISSN)

Vol. 21 1 378-384

Ämneskategorier

Elektroteknik och elektronik

DOI

10.1109/TPWRS.2005.857837