An experimental investigation of the accuracy of thermal response tests used to measure ground thermal properties
Artikel i vetenskaplig tidskrift, 2011

This paper first reports on the results of thermal response tests conducted with laboratory-grade instrumentation and equipment for a borehole system consisting of nine groundwater-filled boreholes, each about 80 m deep. The ground thermal properties, including the undisturbed ground temperature, the thermal conductivity and the borehole thermal resistance, are determined for each of the nine boreholes using standard evaluation methods. Comparison of the results of the ground thermal properties of the nine boreholes provides meaningful insight into the uncertainty issue of the thermal response tests. The ground thermal conductivity and the borehole thermal resistance estimations of nine boreholes are then used to investigate the sensitivity of the design of borehole systems to the random variations in the estimated thermal properties. The paper also presents the effects of the test duration and the heat injection rate on the estimated ground thermal properties when conducting thermal response tests.

thermal response tests

accuracy

experimental investigation

ground thermal properties

Författare

Saqib Javed

Chalmers, Energi och miljö, Installationsteknik

Per Fahlén

Chalmers, Energi och miljö, Installationsteknik

Jeffrey D Spitler

ASHRAE Transactions

0001-2505 (ISSN)

Vol. 117 1 13-21

Ämneskategorier

Övrig annan teknik

Mer information

Skapat

2017-10-07