Wind Farm Configuration and Energy Efficiency Studies - Series DC versus AC Layouts
Doktorsavhandling, 2006

In this thesis, the design and control of a wind farm utilizing series-connected wind turbines with a DC output has been evaluated. The advantage is that a suitable DC voltage level, appropriate for transmission of the generated power directly, without using a large centralized DC/DC converter, can be obtained. This is achieved by series-connecting a number of wind turbines. In addition, the energy production using various wind turbines and wind park layouts have been investigated. Furthermore, the energy production costs have been determined. Finally, the limiting factors for the installation of smaller wind parks have been evaluated. For instance, when dynamic power pulsations have to be considered, from a power quality point of view, when a wind energy installation is to be connected to the grid. The results found are that the uneven power production from the individual wind turbines creates design as well as control difficulties for the wind farm with series-connected wind turbines. A control scheme for the wind turbines is proposed and investigated in this thesis. It is found that the proposed control scheme manages to safely operate the wind farm, even when large deviations in the individual power production of the turbines exist. A down-scaled prototype has been built, representing one wind turbine unit, and the base current control ability was verified experimentally. Moreover, it is found that it is necessary to design the individual wind turbine converters for a voltage level of about 35 % higher than the nominal voltage. Otherwise there will be a substantial energy loss due to the uneven power production from the individual wind turbines that occurs in actual installation. In addition, it is found that the series dc wind park has a good economical potential, since it eliminates the need for an offshore platform in the wind park. Finally, the electrical limiting factors for the installation of wind farms are determined using field experimental data. For instance, it is shown that for a wind park of about 10 wind turbines, the power pulsations are "smoothened" sufficiently so that the flicker emission never will be the limiting factor, even for fixed-speed turbines, when a wind energy installation is connected to a network. Worth mentioning is that it was found that the summation formula for flicker given in IEC 61400-21 can give a flicker prediction that is too low.

10.00 VD-room, Hörsalsvägen 11, Chalmers
Opponent: Professor, Frede Blaabjerg, Ålborg University, Denmark

Författare

Stefan Lundberg

Chalmers, Energi och miljö, Elkraftteknik

Energy Efficiency Comparison of Electrical Systems for Wind Turbines

Nordic Workshop on Power and Industrial Electronics,;(2002)

Paper i proceeding

Evaluation of wind farm layouts

Nordic Workshop on Power and Industrial Electronics,;(2004)

Paper i proceeding

A DFIG wind turbine ride-through system. Influence on the energy production

Wind Energy,;Vol. 8(2005)p. 251-263

Artikel i vetenskaplig tidskrift

Electrical limiting Factors for Wind Energy Installations in Weak Grids

International Journal of Renewable Energy Engineering,;Vol. 3(2001)p. 305-310

Artikel i vetenskaplig tidskrift

Flicker contribution from wind turbine installations

IEEE Transactions on Energy Conversion,;Vol. 19(2004)p. 157-163

Artikel i vetenskaplig tidskrift

System efficiency of a DC/DC converter based wind turbine grid system

Nordic Wind Power Conference, 22-23 May 2006, Espoo, Finland,;(2006)

Övrigt konferensbidrag

Ämneskategorier

Annan elektroteknik och elektronik

ISBN

978-91-7291-884-9

Doktorsavhandlingar vid Chalmers tekniska högskola. Ny serie: 2565

10.00 VD-room, Hörsalsvägen 11, Chalmers

Opponent: Professor, Frede Blaabjerg, Ålborg University, Denmark

Mer information

Skapat

2017-10-07