The compression/absorption heat pump cycle – conceptual design improvements and comparisons with the compression cycle
Artikel i vetenskaplig tidskrift, 2002

Performance improvement of an industrial single-stage compression/absorption heat pump (CAHP) using an ammonia/water mixture as the working fluid has been studied theoretically. By allowing a higher absorber pressure (40 bar) than the highest design pressure of today's screw compressors (25 bar), higher COPs could be obtained. Longer falling-film tubes in the vertical shell-and-tube absorber and desorber also increased the COP. These two modifications together increased the COP of the CAHP by 10%. The improved design has a lower optimal absorber glide (temperature difference due to composition change in absorber) and reduced solution heat exchanger sizes. The study was performed with a constant total area. Furthermore, the CAHP performance was studied for five heating cases. Its performance was compared to that of a two-stage compression heat pump (CHP) using isobutane as working fluid, on the basis of approximately equal investment cost. It could be concluded that only heating cases where both the sink and the source temperature changes are high (>20 K) give superior performance for the CAHP.

Heat pump

Water

Ammonia

Absorption

Författare

Magnus Hultén

Institutionen för värmeteknik och maskinlära

Thore Berntsson

Institutionen för värmeteknik och maskinlära

International Journal of Refrigeration

1404-7098 (ISSN)

Vol. 25 4 487-497

Ämneskategorier

Kemiteknik

DOI

10.1016/S0140-7007(02)00014-2

Mer information

Skapat

2017-10-06