Humidity Dependent Charge Formation in Air under DC field Below Partial Discharge Inception
Paper i proceeding, 2024

This study investigates the influence of humidity, electric field strength, and electrode geometry on charge formation and accumulation dynamics at electrode-air-polymer interfaces under DC conditions below the partial discharge inception level. Utilizing a structured test matrix with varying voltages and electrode radii, experiments were conducted in a controlled environment where humidity levels ranged from 40% to 90%. The results reveal that lower voltage levels and larger electrode radii significantly heighten sensitivity to humidity changes, affecting charge accumulation patterns at the dielectric-air interface. Notably, high humidity conditions (98% RH) demonstrated that water condensation on electrodes can inhibit charge generation. Surface potential measurements with a Kelvin probe is utilized to quantify these effects, highlighting the complex interaction among air humidity, electric field strength, and time in influencing charge formation. This study enhances the understanding of charge dynamics critical for improving the reliability and performance of HVDC insulation systems.

Författare

Jin Wang

Chalmers, Elektroteknik, Elkraftteknik

Daniel Svensson

Chalmers, Teknikens ekonomi och organisation, Science, Technology and Society

Olof Hjortstam

Chalmers, Elektroteknik, Elkraftteknik

Hitachi

Xiangdong Xu

Chalmers, Elektroteknik, Elkraftteknik

Annual Report - Conference on Electrical Insulation and Dielectric Phenomena, CEIDP

00849162 (ISSN)


9798350366679 (ISBN)

2024 IEEE Conference on Electrical Insulation and Dielectric Phenomena, CEIDP 2024
Auburn, USA,

Ämneskategorier (SSIF 2025)

Annan elektroteknik och elektronik

DOI

10.1109/CEIDP61745.2024.10907604

Mer information

Senast uppdaterat

2025-04-01