Energy recovery in air handling systems in non-residential buildings - design considerations
Paper i proceeding, 2010

Heating of supply air and drive energy to fans and pumps predominate the energy use of HVAC systems in non-residential buildings in cold, dry climates. Hence heat recovery and the effect on fan energy is of interest whereas recovery of cooling and moisture is less of an issue. This study looks at dedicated outdoor air systems with a run-around loop heat recovery or an enthalpy wheel heat recovery. In nonresidential buildings heat recovery with full capacity is used only during a part of the year but it still causes a pressure drop in the air round. In this situation the most energy efficient system with the highest temperature efficiency if one considers the If the value of electricity, compared to the value of heat, handling unit all year is not always the one penalty in fan energy is taken into account, the temperature efficiency might be even less important. In this case-study the enthalpy wheel with the lowest temperature efficiency was the most energy efficient choice on a system level. The same applies for the run-around loop systems, where the run-around loop with the lower temperature efficiency gave the better result. In the case of run-around loop systems there are different strategies for capacity control of the liquid flow to obtain optimal operation. Common alternatives are constant flow with variable temperature by means of a shunt group and variable flow by means flow control of a variable power is used compared to of two-way valve. A more energy efficient way is direct speed pump. In direct flow control a much smaller pump valve control. Shunt groups, in particular, result in pump power that is constant and unaffected by the real demand. Calculations based on measurements on a run-around loop system with direct flow control during three months show that the pump power after optimizing the flow can be reduced by 80 %.

Författare

Caroline S Markusson

Chalmers, Energi och miljö, Installationsteknik

L. Jagemar

Per Fahlén

Chalmers, Energi och miljö, Installationsteknik

ASHRAE Transactions

0001-2505 (ISSN)

Vol. 116 154-167

Ämneskategorier

Husbyggnad

Mer information

Skapat

2017-10-07