Frequency evaluation of the Nordic power system using PMU measurements
Artikel i vetenskaplig tidskrift, 2017

This study investigates the frequency behaviour in the Nordic power system (NPS) utilising phasor measurement units (PMUs) from different locations in the system. Different metrics are selected or proposed to quantify the system frequency response in case of major disturbances and of daily normal operations. Based on the collected PMU data, there are on average 17.5 major, generator disconnection related, disturbances per year. The maximum absolute rate of change of frequency exceeds 0.1 Hz/s for 20% of these disturbances. The average frequency nadir falls to 49.7 \Hz, and the average time to nadir is about 8.7 s. If wind turbines were to be requested to provide inertia support to the system, these four metrics indicate how often, how fast, for how much and for how long the wind turbines should act. Moreover, during daily normal operations, the system has in general longer duration of over-frequency (f > 50.1 Hz) than under-frequency (f < 49.9 Hz). These frequency deviations are observed to occur around the hourly clearing of the Nord Pool Spot market and, especially during the hours between 05:00 and 08:00. In order to improve the frequency quality, the Nordic system operators tested and implemented an automatic frequency restoration reserve (aFRR) in addition to the existing manual one. Based on a frequency evaluation, this aFRR is needed most during 4:45-08:15 and 22:00-23:30 o'clock in 2012 in the NPS. © 2017, The Institution of Engineering and Technology.

Författare

Mattias Persson

Chalmers, Energi och miljö, Elkraftteknik

Peiyuan Chen

Chalmers, Energi och miljö, Elkraftteknik

IET Generation, Transmission and Distribution

1751-8687 (ISSN) 1751-8695 (eISSN)

Vol. 11 11 2879-2887

Drivkrafter

Hållbar utveckling

Styrkeområden

Energi

Ämneskategorier

Reglerteknik

DOI

10.1049/iet-gtd.2017.0095

Mer information

Skapat

2017-10-07