Induction ratio of active chilled beams - Measurement methods and influencing parameters
Journal article, 2016

In active chilled beams, primary air from the air handling unit induces room air which passes a cooling coil before it mixes with the primary air and discharges into the room. The ratio of induced room air flow to the primary air flow is the induction ratio (IR). Knowledge about the IR is important when modelling cooling capacity as well as temperature and velocity of the air discharged from the beam. Most previous studies of the behavior of IR are focusing on the influence of primary air flow. The purpose of the work presented in this paper is to investigate whether other operating conditions also influence the IR. Three methods of determining the IR are compared in order to strengthen the conclusions. The results indicate that the IR is influenced by the chilled water temperature due to buoyant forces. Novel methods of determining the IR are presented and it is concluded that current methods may lead to overestimation.

Induction ratio

Measurements

Entrainment ratio

Active chilled beams

Author

Peter J Filipsson

Chalmers, Civil and Environmental Engineering, Building Services Engineering

Anders Trüschel

Chalmers, Civil and Environmental Engineering, Building Services Engineering

Jonas Gräslund

Chalmers, Civil and Environmental Engineering, Building Services Engineering

Jan-Olof Dalenbäck

Chalmers, Civil and Environmental Engineering, Building Services Engineering

Energy and Buildings

0378-7788 (ISSN)

Vol. 129 445-451

Areas of Advance

Building Futures (2010-2018)

Energy

Subject Categories

Building Technologies

DOI

10.1016/j.enbuild.2016.08.024