Intelligent Video Surveillance for Detecting Snow and Ice Coverage on Electrical Insulators of Power Transmission Lines
Paper i proceeding, 2009
One of the problems for electrical power delivery through
power lines in northern countries is when snow or ice accumulates on electrical insulators. This could lead to snow or ice-induced outages and voltage collapse, causing huge economic loss. This paper proposes a novel real-time intelligent surveillance and image analysis system for detecting and estimating the snow and ice coverage on electric insulators using images captured from an outdoor 420 kV power transmission line. In addition, the swing angle of insulators is estimated, as large swing angles due to wind cause short circuits. Hybrid techniques by combining histogram, edges, boundaries and cross correlations are employed for handling a broad range of scenarios caused by changing weather and lighting conditions. Experiments have been conducted on the captured images over several month periods. Results have shown that the proposed system has provided valuable estimation results. For image pixels related to snows on the insulator, the current system has yielded an average
detection rate of 93% for good quality images, and 67.6% for images containing large amount of poor quality ones, and the corresponding average false alarm ranges from 9% to 18.1%. Further improvement may be achieved by using video-based analysis and improved camera settings.
electric insulator surveillance
swing angle
insulator image analysis.
snow detection
ice detection