Chilled water temperature control of self-regulating active chilled beams
Paper i proceeding, 2020

The flow rate of chilled water in a self-regulating active chilled beam is constant without respect to the actual cooling load. The cooling capacity is instead determined by the room temperature, which gives rise to the self-regulating effect, and also by the centrally controlled chilled water temperature, which is the focus of this paper . Previous studies have emphasized the benefit of avoiding room-level control equipment, but also highlighted the risk of overcooling with detrimental effects on thermal climate and energy demand. Overcooling may be avoided by supply temperature control, but strategies have not yet been studied in systems operating in cooling mode only. Simulations are carried out with IDA ICE. The results show that overcooling is effectively avoided by proper control of the chilled water temperature. Desired thermal climate is achieved and the energy demand is in the same order of magnitude as in a system with individually and ideally PI-controlled active chilled beams.

self-regulation

active chilled beams

simulation

supply temperature control

IDA ICE

Författare

Peter J Filipsson

Chalmers, Arkitektur och samhällsbyggnadsteknik, Installationsteknik

Anders Trüschel

Chalmers, Arkitektur och samhällsbyggnadsteknik, Installationsteknik

Jonas Gräslund

Chalmers, Arkitektur och samhällsbyggnadsteknik, Installationsteknik

Jan-Olof Dalenbäck

Chalmers, Arkitektur och samhällsbyggnadsteknik, Installationsteknik

SINTEF Proceedings

2387-4295 (ISSN)

Vol. 5 230-237
978-82-536-1679-7 (ISBN)

BuildSIM - Nordic 2020
Oslo, Norway,

Självverkande kylbaffelsystem

Svenska Byggbranschens Utvecklingsfond (SBUF) (12813), 2013-05-01 -- 2016-12-31.

Drivkrafter

Hållbar utveckling

Ämneskategorier

Energiteknik

Energisystem

Husbyggnad

Styrkeområden

Energi

Mer information

Senast uppdaterat

2022-04-22