Quasi-Dynamic Modelling of DC Operated Ground-Source Heat Pump
Paper i proceeding, 2020

The performance of a conventional ground-source heat pump (GSHP) has been measured in the laboratory with alternating current (AC) and direct current (DC) operation using the standardised points from EN14511:2018. The results from these measurements have been used to modify a variable speed heat pump model in IDA Indoor Climate and Energy (ICE) and the annual performance of AC and DC operation have been simulated for an entire year’s operation at two geographical locations in Sweden. Results show that the energy savings with DC operation from laboratory measurements span between 1.4–5.2% and when simulating the performance for an entire year’s operation, the energy savings vary between 2.5–3.4%. Furthermore, the energy savings from the simulations have been compared to the bin method described in EN14825:2018.

Heat pump

Building Simulation

Energy Savings

Direct current

Författare

Patrik Ollas

Chalmers, Elektroteknik, Elkraftteknik

Caroline S Markusson

Installationsteknik

Torbjörn Thiringer

Chalmers, Elektroteknik, Elkraftteknik

SINTEF Proceedings

2387-4295 (ISSN)

Vol. 5 208-213

BuildSIM Nordic 2020
Online, Norway,

Drivkrafter

Hållbar utveckling

Ämneskategorier

Energiteknik

Energisystem

Marin teknik

Styrkeområden

Energi

Mer information

Senast uppdaterat