Utvärdering av system för ersättningsluft vid spiskåpeforcering Tekniktävling - Ventilation i energieffektiva flerbostadshus - Etapp 2
Rapport, 2023
The solutions were tested in a test chamber with low leakage through its envelope. It has smaller dimensions than real apartments. The smaller size means that the pressure changes that occur in the chamber will be faster than they would be in a real apartment. Thus, the technology solutions have been tested under slightly stricter conditions than is normal in real buildings.
The measurements show that both solutions are able to limit the negative pressure indoors so that it becomes higher than 10 Pa just briefly. The solutions are considered robust and long-term stable as they were tested for at least 200 cycles without any malfunction being observed. Over time, however, dust will accumulate on the dampers, which could affect their functioning; that they get stuck and/or that they do not close tightly in the closed position. However, this has not been tested in the current project. Regular inspection and cleaning will be required, especially of the solution installed as an outdoor air valve/supply air radiator, as the damper in that case is exposed to unfiltered outdoor air. The rather slow change in the damper position contributes to the solutions being judged as robust
Residential ventilation
building envelope
pressure difference
mechanical exhaust
air tightness
control system