Checking of ventilation rates by CO2 monitoring.
Paper i proceeding, 1996

The present paper presents results from measurements of outdoor airflow rates and air change rates carried out simultaneously with measurements of the indoor concentration of carbon dioxide (CO2 ) . The measurements were made both under controlled laboratory conditions and in the field. The field experiments were performed in a conference room, an assembly hall and an office room, and the laboratory investigation was carried out in a 19 m³ test chamber. CO2 measurements can be successfully used to estimate the outdoor airflow rate in occupied rooms, but it is vital that the methodology takes into consideration a number of possible sources of errors. For example, it can not be presupposed that steady-state conditions prevail. However, inaccuracies due to non steady-state conditions may be reduced by a thorough analysis of the measurement results. Furthermore, it is demonstrated how the air change rate can be determined using a method based on analysis of the CO2- concentration decay in a room.

Outdoor air

ventilation rate

Carbon dioxide

Test chamber

Författare

Lars Ekberg

Chalmers, Bygg- och miljöteknik, Installationsteknik

Ove Strindehag

Chalmers, Bygg- och miljöteknik, Installationsteknik

Publicerad i

17th AIVC Conference "Optimum Ventilation and Air Flow Control in Buildings"

Saknas (ISSN) Saknas (eISSN)

Konferens

17th AIVC Conference "Optimum Ventilation and Air Flow Control in Buildings", Gothenburg, Sweden, 17-20 September 1996
, Sweden, 1996-09-16 - 1996-09-19

Kategorisering

Drivkrafter

Hållbar utveckling

Styrkeområden

Energi

Ämneskategorier (SSIF 2011)

Husbyggnad

Mer information

Skapat

2024-02-10