On the risk for subsynchronous control interaction in Type 4 based wind farms
Artikel i vetenskaplig tidskrift, 2019

The aim of this paper is to investigate the risk for subsynchronous control interaction (SSCI) in Type 4 based wind farms connected to series-compensated transmission lines. For this purpose, the frequency-dependent input admittance of the turbine is derived and the power-dissipation properties of the turbine are used to identify those control parameters and operating conditions that mainly impact the behavior of the wind turbine in the subsynchronous frequency range. It is shown that the Type 4 wind turbine presents a non-dissipative behavior in the subsynchronous frequency range, which is mainly dependent on the speed of response of the synchronization loop, the reactive power controller and the active-power output. For a radial connection, a high series-compensation level also negatively impacts the risk for SSCI. The generalized Nyquist criterion is used to assess the stability of the system and the theoretical findings are verified using detailed time-domain simulations.

Wind power

Subsynchronous Control Interaction (SSCI)

Type 4 wind turbine

Voltage Source Converter (VSC)

Subsynchronous Resonance (SSR)

frequency domain analysis

Författare

Mebtu Bihonegn Beza

Chalmers, Elektroteknik, Elkraftteknik

Massimo Bongiorno

Chalmers, Elektroteknik, Elkraftteknik

IEEE Transactions on Sustainable Energy

1949-3029 (ISSN) 19493037 (eISSN)

Vol. 10 3 1410-1418 8585100

Drivkrafter

Hållbar utveckling

Styrkeområden

Energi

Ämneskategorier

Elektroteknik och elektronik

DOI

10.1109/TSTE.2018.2889181

Mer information

Senast uppdaterat

2022-04-05