Effect of the paste–anode interface under impressed current cathodic protection in concrete structures
Artikel i vetenskaplig tidskrift, 2018
Calcium dissolution was found with an average thickness of 0.34 mm around the anode after charges of 6*10^6 C/m2 were applied, equivalent to applying 4 mA/m2 of anode surface for 30 years. Calcium dissolution resulted in a white zone around the anode, where the calcium silica ratio was lowered and almost no crystal phase was observed. NMR results show clear Q3 and Q4 peaks in the white zone, which contained extended branched and networked structures of hardened cement paste. An increased resistance caused by the formation of the white zone may eventually make the system fail because of insufficient current densities. CFRP has been proven suitable for ICCP application even at a current density of 4 A/m2 of anode surface.
calcium dissolution
cathodic protection
accelerated test
CFRP anode
paste–anode interface
microstructure
Författare
Emma Zhang
Chalmers, Arkitektur och samhällsbyggnadsteknik, Byggnadsteknologi
Luping Tang
Chalmers, Arkitektur och samhällsbyggnadsteknik, Byggnadsteknologi
Diana Bernin
Göteborgs universitet
Helen Jansson
Chalmers, Arkitektur och samhällsbyggnadsteknik, Byggnadsteknologi
Materials and Corrosion - Werkstoffe und Korrosion
09475117 (ISSN) 1521-4176 (eISSN)
Vol. 69 8 1104-1116Utveckling av hållbara elektrokemiska korrosionsskyddssystem for armerade betongkonstruktioner (DOSECOPS)
Europeiska kommissionen (EU) (EC/FP7/294955), 2012-07-01 -- 2016-06-30.
Betongtäckskikt med hybridfunktioner - ett nytt sätt att åstadkomma hållbara armerade betongkonstruktioner med låg cementhalt
Formas (2011-1520), 2012-03-15 -- 2015-03-15.
Styrkeområden
Building Futures (2010-2018)
Materialvetenskap
Ämneskategorier
Infrastrukturteknik
Materialkemi
Annan kemi
Kompositmaterial och -teknik
Korrosionsteknik
Den kondenserade materiens fysik
Infrastruktur
Chalmers materialanalyslaboratorium
DOI
10.1002/maco.201709908