CO2, temperature and RH in Swedish primary school classrooms with and without automatic window operation
Paper i proceeding, 2025

Extensive field measurements have shown that school buildings ventilated naturally often suffer from insufficient air change rates (ACR) and elevated CO2 concentrations, which can result in decreased alertness, lower school performance and increased absenteeism of children. Moreover, the variable character of natural ventilation can lead to unwanted fluctuations in thermal environment, which is highly dependent on the actual window operation conducted by the classroom staff, and outdoor weather conditions. Mechanical supply and exhaust ventilation systems, if designed and operated correctly, can provide sufficient ACR, and positively contribute to desired thermal conditions. However, their installation is not always possible due to various reasons. In such case, it is necessary to explore alternatives to ensure sufficient ventilation rates and acceptable thermal environment. This paper presents an analysis of continuous CO2 concentration, temperature, and relative humidity (RH) measurements conducted in 45 Swedish primary school classrooms, equipped with different ventilation systems. The focus of the analysis is on the classrooms equipped with automatic window opening and mechanical exhaust ventilation. The measurements were performed during heating season and during one school week. Various statistical metrics were calculated, as well as the duration of periods when the investigated IEQ variables exceeded recommended value or were outside the recommended range. The variability of the thermal environment was also explored. All these results were compared with the remaining classrooms in the sample using different ventilation strategies. The classrooms with automatic window operation showed substantially lower CO2 concentrations than the classrooms with manual window opening, regardless of whether these had natural ventilation or mechanical exhaust ventilation. The CO2 concentrations were closer to the CAV/VAV classrooms. Temperature and RH were generally within acceptable ranges. Thus, the results suggest that automated window opening systems can improve the performance of natural and mechanical exhaust systems. The paper also addresses potential limitations and risks connected to such solutions.

Meachanical ventilation

Indoor climate

Iaq

Natural ventilation

Field monitoring

Författare

Blanka Cabovska

Chalmers, Arkitektur och samhällsbyggnadsteknik, Installationsteknik

Despoina Teli

Chalmers, Arkitektur och samhällsbyggnadsteknik, Installationsteknik

Jan-Olof Dalenbäck

Chalmers, Arkitektur och samhällsbyggnadsteknik, Installationsteknik

Lars Ekberg

Chalmers, Arkitektur och samhällsbyggnadsteknik, Installationsteknik

Sarka Langer

Chalmers, Arkitektur och samhällsbyggnadsteknik, Installationsteknik

E3S Web of Conferences

25550403 (ISSN) 22671242 (eISSN)

Vol. 672 01031

The 17th ROOMVENT Conference (ROOMVENT 2024)
Stockholm, Sweden,

Vägar till bättre inomhusmiljö i svenska skolor

Formas (2017-01015), 2018-01-01 -- 2020-12-31.

Energiprestanda och innemiljö i skolbyggnader

Energimyndigheten (46866-1), 2019-01-01 -- 2021-12-31.

Drivkrafter

Hållbar utveckling

Ämneskategorier (SSIF 2025)

Byggprocess och förvaltning

Styrkeområden

Energi

Hälsa och teknik

DOI

10.1051/e3sconf/202567201031

Mer information

Senast uppdaterat

2025-12-21